Error Code E CH
High-Side Cycle Refrigerant Leak / Sealed System Problem
Moderate
Address soon - your appliance may not work properly
Also displayed as: E CH
How to Fix
- 1
Use LG SVC App Step 1 to determine if problem is compressor, sealed system, or customer emotional fault. Without SVC App, use temperature gun.
- 2
Check PCB output voltages to rule out PCB fault.
- 3
Measure high-pressure side (drier) and low-pressure side (compressor process pipe) pressures. Check return time to equalization: if more than 15 minutes, sealed system is blocked.
- 4
Check equalization pressure to confirm refrigerant charge level.
- 5
Use SVC App Step 2 or charge nitrogen/R134a to locate leak.
- 6
Inspect high-pressure side parts: condenser, drier, condenser outlet, drier inlet, drier outlet.
- 7
If no high-pressure leak found, check low-pressure side: evaporator inlet/outlet, suction pipe.
- 8
Repair leak, replace drier, and recharge with R600a (60g).
- 9
After repair, error clears automatically when freezer reaches 14°F or below.
- 10
Force-clear error if needed: with door open, press F key + R key 3 times.
- 11
Check for UV dye at next visit to confirm no re-leak.
This Error Applies To
LG LRFS28XB Series Refrigerators