Error Code E CL
Low-side cycle leakage (sealed system)
Moderate
Address soon - your appliance may not work properly
How to Fix
- 1
Verify error using SVC App Step 1 to determine if sealed system or compressor issue. Check evaporator temperature.
- 2
Check PCB voltage outputs; if abnormal, replace PCB.
- 3
Measure pressures and equalization time after power off. If equalization takes more than 15 minutes, restriction is confirmed.
- 4
If equalization pressure is above 20 psi, compressor is defective. Replace compressor.
- 5
If equalization pressure is 20 psi or below, refrigerant has leaked. Begin with low-pressure side leak inspection (evaporator, suction pipe) using bubble test or leak detector.
- 6
If low-side leak found, replace leaking part plus compressor and drier (moisture contamination).
- 7
If no low-side leak found, inspect high-pressure side (condenser, drier, compressor discharge).
- 8
If high-side leak found, replace the part and drier.
- 9
If no leak found, install UV drier; inspect at next visit with UV light.
- 10
Error code clears automatically when freezer temperature reaches 14°F or below after repair.